- Type
- 30
- Procedure
- neg-w-call
- Ref. number
- 20350-2026
- Estimated value
- 558,280 EUR
- CPV
- 31682300
The Contract is for the delivery, installation and Site Acceptance Testing (SAT) of 1 (one) medium-voltage air-insulated switchgear to be installed in the substation for the connection of the Battery Energy Storage Syste…
m (BESS) to the main MV switchgear in Avedøre Power Plant in Denmark to the Contracting Entity for the Project. General characteristics of the switchgear: • Rated voltage: 17.5 kV three-phase • Operating voltage: 11.1 kV • Frequency: 50 Hz • Insulation level: 38 kV – 50 Hz, 1 min • BIL: 95 kV – 1.2/
50 μs • Busbar rated current: 2500 A • Short-circuit current: 63 kA / 1 s • Internal arc classification: AFRL - 63 kA / 0.5 s • Rated current of circuit breakers: • Incomer cubicle: 2500 A • Feeder cubicles: 630 A • Auxiliary services cubic