- Type
- 30
- Procedure
- neg-wo-call
- Ref. number
- 744257-2024
- Estimated value
- 1,055,000 EUR
- CPV
- 31174000
Procurement and delivery of one three-phase, oil-immersed, air-cooled power transformer with load tap changer with the following specifications: Rated power: 56 MVA Nominal system voltages: 50/20 kV Rated voltage, primar…
y winding: 50 kV Rated voltage, secondary winding: 20 kV Voltage regulation, primary/secondary: 50 ± 8×1,25% / 20 kV Short Circuit Impedance, primary/secondary: 12% Vector group: Dyn 5 Frequency: 50 Hz Cooling: ONAN Maximum sound power level: 78 dB(A) at full load, including winding noise.
Procurement and delivery of one three-phase, oil-immersed, air-cooled power transformer with load tap changer with the following specifications: Rated power: 56 MVA Nominal system voltages: 50/20 kV Rated voltage, primar